Product features:
The performance of cross-linked polyethylene insulated (flame retardant) power cable conforms to the national standard GB / t12706.1-2008, and ie60502-2004 is equivalent. The flame retardant combustion conforms to the national standard
GB / t18380.3-1998 is equivalent to lec60332-1997.
Usage characteristics:
The rated working voltage uo / U of the cable is 0.6/1kv
Long term allowable working temperature of cable conductor: 90 ℃
Short circuit temperature of cable conductor: < 250 ℃, duration: < 5S
Bending radius of cable laying: single core cable > 20 times of cable outer diameter, multi-core cable > 15 times of cable outer diameter.
When the cable is laid, the temperature shall not be lower than 0 ℃. When the temperature is lower than 0 ℃, the temperature shall be increased in advance, and the cable laying is not limited by the drop level.